FanTech SH 704 HRV


The SMALLEST HEAT RECOVERY & ENERGY RECOVERY UNITS in the INDUSTRY

Compact HRV with easy-mount, wall bracket. Brings a continuous supply of fresh air into a home while exhausting an equal amount of contaminated air. HRVs use what is called a “sensible” heat recovery core. This special core transfers heat from the exhaust air stream to the incoming air stream. Fresh incoming air is tempered by the heat that is transferred from the outgoing air to save on energy costs. The SH 704 is equipped with automatic defrost mechanisms so even if you live in the coldest climates you can use your HRV all year long.
    SH 704 Features
  • Super Compact Size
  • Includes Easy-Mount Wall Bracket
  • Aluminum Heat Recovery Core
  • 4" (100mm) Duct Connections
  • No Balancing Required
  • Easy Access Service Door
  • Automatic Exhaust Defrost
  • wgt: 25Lbs
  • 3' power cord
  • Core Removes Easily
  • Single Speed Ventilation



    Accessories
  • FDT7 - 7 Day Digital Programmable Timer
  • COM 4P - 4” Weather Hoods (1 supply & 1 exhaust)
  • FEL 4 - 4” 90° Elbow
  • CG4 - 4” Adjustable Grille


SPECIFICATIONS:
Case 24 gauge galvanized steel. Baked powder coated paint, antique white. Cabinet fully insulated with 1” aluminum foil-face high density polystyrene foam to prevent condensation and meet the requirements of the UL 94HF.

MOTORS:
Two (2) German-manufactured, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed ball bearings guarantee long life and maintenance-free operation. Seven (7) year warranty. Steep fan curves requires no balancing of airflows.

CORE:
Aluminum heat recovery core configured for efficient, cross-flow ventilation. Core is 8.5” x 8.5” with a 8” depth. Cores are manufactured by Fantech to withstand extreme temperature variations.

FILTERS:
Two washable electrostatic panel type air filters (8.5”x8”x.125”)

CONTROLS:
Unit is designed to operate continuously on an single speed. Tech support for possible intermittent, line-voltage options

Defrost:
The automatic defrost cycle consists of a fan shutdown. When the supply air stream temperature goes below 23°F, the supply motor shuts down while the exhaust motor continues to ventilate. Ambient air is passed through the unit for a period of 3 or 5 mintes. The supply motor will then restart and run at the present speed. This fan shutdown defrost cycle contunes until the supply air stream rises above 23°F.

SERVICEABILITY:
Core, filters, motors and drain pan can be easily accessed through latched door. Core conveniently slides out on new easy glide core guides. 10” of cleanace is recommended for removal of core.

DUCT CONNECTION:
4” steel duct connections with rubber gasket for easy sealing.

DRAIN:
1/2” OD( outside diameter) drain spout (provided) and the entire bottom of unit covered by pan.

WARRANTY: